Brand |
SIERRA |
Items |
2K Standard Backup 1/1 HF |
Description |
2KVA/1.6KW, HF Tower, BAT Voltage: 48VDC,1 phase in/1 phase out, with BAT. |
Capacity |
2KVA/1.6KW |
Form Factor |
Tower |
|
Host Machine Specification |
UPS Structure
|
Double Conversion High Frequency Online |
Appearance |
Tower or Rack-Mount Type |
Overall Efficiency (AC-AC) |
> 90% |
Noise (In 2 meters) |
< 50dB |
Working Temp |
0-40°C |
Storage Temp |
-15 ~ 60°C(Without BATs) |
Humidity |
< 95% Non Condensing |
Safety Standard |
GB/T14715 |
EMC Standard |
EN 50091-1/2 |
Protections |
Overload, Short-Circuit, Over Temp., Utility Power Voltage High/low, BAT Voltage High/low |
Parallel Redundancy |
None |
Generator Compatibility |
Available |
DC Start |
Available |
Manual Maintenance Bypass |
None |
Display |
LCD/LED: UPS Status, INV Status, Bypass Status, BAT Status, BAT %, Load %, Fault Messages |
Alarm |
Auto |
Mute |
Auto |
|
Rectifier Specification
|
Input Voltage Range
|
100% Load: 160~300Vac, 50% Load: 115~300Vac |
Input Frequency Range
|
45-65Hz(Auto Tracking) |
Input PF |
0.99 |
THDI |
< 5% |
|
Output Specification |
Output Voltage
|
220Vac |
Output PF |
0.8 |
Output Voltage Regulation |
220Vac±1%(Static Load);220Vac±2%(50-0% Sudden Change);220Vac±3%(100-0% Sudden Change) |
Output Freq.(Online Mode) |
When 46Hz ≤Input Freq.≤ 54Hz,Input Freq.=Output Freq.;When Input Freq.<46Hz or >54Hz, Locked at 50Hz |
Output Freq. (BAT Mode) |
50Hz± 0.2% |
Output Waveform |
Pure Sine wave |
Distortion |
< 1% (Linear Full Load) , < 3% (100% Non-Linear Load) |
Overload |
- > 125%: More than 1 min
- > 150%: 300 ms transfer to bypass
|
Crest Ratio |
3 ∶ 1 |
Efficiency |
> 90% |
Short-Circuit |
Circuit Auto Protection, Output Voltage/Current 0 |
Output Abnormal |
INV Output Auto-Locked Protection |
Noise Suppression |
EMI/RFI Wave filter |
BAT Low |
Shutdown Protection |
Dynamic Response |
3% at full load,recovering in 20ms |
Auto-Restart |
Available |
Software Control |
Available |
|
Bypass Specification |
Static Bypass Transfer Time |
0ms |
Static Bypass Range |
80Vac± 5% ~285Vac±5% |
Bypass -> INV Transfer Time |
2ms |
|
Battery Specification |
Type
|
Sealed Lead Acid Maintenance Free |
Std. Model Rated Volts/Units
|
12V/7Ah×4/6P |
Backup Time |
5-15min |
Ext. Model Rate Volts/Units |
48Vdc |
Std. Model Charging Current |
1A |
Ext. Model Charging Current |
|
|
Communication Specification |
Communication Port |
Rs232 (Std.);/SNMP/RS485/ Dry Contact (Optional Accessory) |
Remote Software |
Multi-functional Monitoring System, Online and BAT Mode Status, BAT Fault, Remote Control |
|
Physical Specification |
Tower Size (D×W×H)
|
433 × 190 × 318 mm |
Net Weight |
18.523 |